1. Features and Ambient Condition
- Excellent breaking function, long electric life,
continuous breaking times at 50KA short circuit
current:20 times.
- Overhaul check period:>15 years.
- Mechanical endurance >3000 times,relative frequent operation allowed
Good for frequent operation.
- Easy installation, adjustment-free on site.
- Fine earthquake-proof: be able to withstand horizontal
acceleration of 0.5g and vertical acceleration of 0.25g.
Applicable for area with frequent earthquake.
- Altitude¡Ü2000m, ambient temperature-40¡«50.
|
 |
|
|
2.Technical
data:
|
Item
|
Unit
|
LW6-72.5
|
LW6--126
|
LW6-145
|
LW6-170
|
|
Rated voltage
|
KV
|
72.5
|
126
|
145
|
170
|
|
Rated current
|
A
|
2500
|
3150
|
3150
|
3150
|
|
Rated gas pressure(SF6,20¡ãC)
|
MPa
|
0.6/0.4
|
|
Rated breaking current
|
KA
|
50/40/31.5
|
|
Rated short time withstand current(3s)
|
KA
|
50/40
|
|
Rated peak withstand current
|
KA
|
125/100
|
|
Accumulated breaking current
|
KA
|
4200kA
|
|
Breaking time
|
ms
|
¡Ü60
|
|
Power frequency withstand voltage(rms,1min )
|
KV
|
160+(42)/160
|
250+(72)/250
|
303+(42)/303
|
325/365
|
|
Lightning impulse withstand voltage(full wave 1.2/50¦Ìs)
|
KV
|
350+(60)/350
|
550+(103)/550
|
722/722
|
750/750
|
|
Withstand voltage at zero gas gauge pressure(rms, 5min)
|
KV
|
84/84
|
146/146
|
168/168
|
175/175
|
|
Permissible load on wiring terminal
|
Horizontal
|
N
|
750
|
1250
|
1500
|
|
Transverse
|
500
|
750
|
1000
|
|
Vertical
|
750
|
1000
|
1250
|
|
|
| |
|
|