Item
|
Unit
|
Data
|
|
Rated voltage
|
kV
|
72.5
|
126
|
145
|
|
Rated current
|
A
|
3150
|
|
Rated frequency
|
Hz
|
50
|
|
Altitude
|
M
|
1000
|
|
Ambient temperature
|
¡æ
|
-25¡«+40 -40¡«+40
|
|
Relative humidity
|
%
|
Day average:¡Ü100 Month average:¡Ü95
|
|
Seismic resistance
|
Degree
|
¡Ü9
|
|
Power frequency withstanding voltage
(rms), 5min, zero SF6 Gauge pressure, to earth and across break
|
kV
|
¡Ý55
|
110
|
|
Insulation level, secondary circuit(1min)
|
V
|
2000
|
|
Bay width
|
M
|
1.5
|
|
Bay weight
|
kg
|
5020
|
|
SF6 leakage rate
|
%
|
<1
|
|
SF6 moisture content
|
CB & CT compartment
|
PPm
|
150/300 (at delivery/in service)
|
|
High speed disconnector compartment
|
|
High speed earthing switch compartment
|
|
Other compartments
|
250/500(at delivery/in service)
|
|
Rated SF6 gas pressure(by volume, 20¡æ)
|
CB & CT compartment
|
Mpa
|
0.6
|
|
Other compartments
|
0.4
|
|
Operating load
|
kN
|
15¡ü, 25¡ý
|
|
Static load
|
kN/m2
|
15
|
|
Crane required for maintenance
|
Capacity
|
kg
|
3000
|
|
Hook Height
|
M
|
¡Ý5.5
|
|
Workshop dimensions
|
H
|
M
|
¡Ý4.5
|
|
W
|